Household AC Contactor
Model Reference

JCH1-25

JCH1-63

NCH8-63

Application
- The product is mainly applicable to a power system of AC 50Hz (or 60Hz), rated working voltage up to 230V, and in a line of application class AC-7a with rated working voltage up to 230V and rated working current up to 20A. It is used to remotely close or/and switch off the line. The product is widely used in dwelling houses, hotels and so on.
- The product is in conformity with the standards: GB 17885 IEC 1095
Normal operation and mounting requirement
- Circumstance temperature -5°C ~ +40°C, average temperature within 24h not exceeding +35°C.
- Altitude above sea level less than 2000 m.
- Humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
- Installation class II
- Pollution class 2.
- Installation method DIN Rail mounting type.
- Product shall be vertically mounted onto standard Din rail 35mm.
Technical Data
Ratings
Utilization category |
Ui (V) | Ui (V~) | Conventional heating current (A) |
Ie (A) | Controlled power (kW) |
AC-1, AC-7a AC-7b | 500 | 230 | 63 | 63/25 | 13/3.8 |
AC-1, AC-7a AC-7b | 500 | 230 | 40 | 40/15 | 8.4/2.4 |
AC-1, AC-7a AC-7b | 500 | 230 | 32 | 32/12 | 6.5/1.9 |
AC-1, AC-7a AC-7b | 500 | 230 | 25 | 25/8.5 | 5.4/1.9 |
AC-1, AC-7a AC-7b | 500 | 230 | 20 | 20/7 | 4/1.2 |
Making and breaking capacity
Utilization category |
Making and breaking conditions | Electrification time (s) |
Interval time (s) |
Operating cycle times |
||
Ic/Ie | Ur/Ue | COSΦ | ||||
AC-1, AC-7a | 1.5 | 1.05 | 0.8 | 0.05 | 10 | 50 |
AC-7b | 8 | 1.05 | 0.45 | 0.05 | 10 | 50 |
Conventional operating performances
Utilization category |
Making conditions | Breaking conditions | Electrification time (s) |
Interval time (s) |
Operating frequency |
||||
Ic/Ie | Ur/Ue | COSΦ | Ic/Ie | Ur/Ue | COSΦ | ||||
AC-1 | 1.0 | 1.05 | 0.8 | 1.0 | 1.05 | 0.8 | 0.05 | 10 | 6000 |
AC-7a | 1.0 | 1.05 | 0.8 | 1.0 | 1.05 | 0.8 | 0.05 | 10 | 30000 |
AC-7b | 6.0 | 1.0 | 0.45 | 1.0 | 0.17 | 0.45 | 0.05 | 10 | 30000 |
Dimensioned
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |